Engineering Guide

Fire Alarm Battery Calculations: A Step-by-Step Guide

FUEGOAI Engineering Team · August 2026 · 7 min read

Every fire alarm submittal needs a battery calculation, and it's one of the first things a plan reviewer checks. NFPA 72 requires fire alarm systems to have a secondary power supply that can carry the system through a power outage and still perform its job at the end of it. This guide walks through the standard calculation method step by step, with a worked example.

Code note: Always confirm the NFPA 72 edition adopted in your jurisdiction and any local amendments with the AHJ. The durations and margins below reflect common practice — your project's code path and the equipment manufacturer's published data govern.

Step 1 — Inventory every device on secondary power

List everything the panel and each power supply must support: the control panel itself, addressable devices (detectors, modules, pull stations), notification appliances, annunciators, communicators, and auxiliary loads. For each, pull two numbers from the manufacturer's datasheet: standby current (normal supervision) and alarm current (full alarm). Quantity matters — 42 detectors at 300 µA is a very different load than 8.

Step 2 — Sum standby and alarm currents separately

Multiply each device's current by its quantity, then total the standby column and the alarm column separately. Remember that notification appliances typically draw nothing in standby but dominate the alarm column, while the panel electronics dominate standby.

Step 3 — Apply the required durations

NFPA 72 defines how long secondary power must carry the system. The commonly applied baseline is 24 hours of standby followed by operation in alarm — 5 minutes for conventional notification, with longer alarm durations (commonly 15 minutes at maximum load) for in-building emergency voice/alarm communication systems. Verify the requirement for your system type and edition.

Step 4 — Convert to amp-hours

The core formula:

Required Ah = (Standby A × 24 h) + (Alarm A × alarm minutes ÷ 60)

Step 5 — Apply a safety margin and select the battery

Multiply the result by a derating factor — 20% (× 1.2) is the widely used industry margin, and some manufacturers' calculation sheets require it — to account for battery aging, temperature, and tolerance. Then round up to the next standard battery size (7, 12, 18, 26, 33, 55 Ah…), checking the panel's charger is rated for the batteries you select.

Worked example

DeviceQtyStandby (A)Alarm (A)
FACP (base panel)10.1500.300
Smoke detectors420.0130.013
Pull stations60.0010.001
Monitor modules80.0030.003
Horn/strobes (NAC)240.0001.440
Total810.1671.757

Standby: 0.167 A × 24 h = 4.00 Ah. Alarm: 1.757 A × 5 min = 0.15 Ah. Subtotal 4.15 Ah × 1.2 = 4.98 Ah → select two 12 V 7 Ah batteries (24 V system).

The mistakes that get submittals bounced

Need submittal-ready fire alarm design — calculations included?

Get a 24-Hour Quote