After thousands of submittals, the same issues keep appearing — in drawings from big firms and small ones alike. Here are the ten we see most, roughly in the order a plan reviewer will find them.

1. Plans, riser, and device counts that don't match

The fastest way to lose a reviewer's confidence. If the riser says 62 devices and the floor plans show 65, everything else on the sheet becomes suspect. Counts must reconcile across plans, riser, and calculations on every revision — not just the first issue.

2. Missing or wrong candela ratings

Strobes need candela ratings selected for the space they cover, and visible notification must meet accessibility requirements. Sheets marked "75cd typ." for every room, regardless of size, are a red flag.

3. Voltage drop beyond the appliance's operating window

Notification appliances have a minimum operating voltage. Long circuits with heavy loads can drop below it at the end of line — the calculation has to be run per circuit, at worst-case source voltage, not estimated.

4. Battery calculations that lag the design

Batteries are sized early, then the design grows. If the calc sheet doesn't reflect the final device counts, the whole package reads as unchecked.

5. Detector spacing that ignores the ceiling

Spacing rules assume smooth, flat ceilings — beams, joists, slopes, and high ceilings all change coverage. Applying listed spacing without looking up at the structure is one of the most common field-discovered errors.

6. No sprinkler coordination

Waterflow and valve-tamper monitoring have to match the actual sprinkler risers, zones, and valves — which means coordinating with the sprinkler contractor's drawings, not guessing from the architectural set.

7. Forgotten HVAC and duct detection coordination

Duct detectors, RTU shutdowns, and damper interfaces require coordination with mechanical. Missing relays and interface modules surface late, as change orders.

8. A vague sequence of operations

The input/output matrix is where the AHJ learns what the system actually does. "General alarm" with no detail on elevator recall, door release, HVAC shutdown, or voice messaging invites comments.

9. Ignoring the AHJ's local submittal requirements

Many jurisdictions publish specific submittal checklists — sheet sizes, required notes, local amendments. A technically sound package that ignores the local checklist still bounces.

10. Circuits designed with zero spare capacity

Loops and NACs loaded to their limit leave nothing for field conditions or tenant changes. Designing in spare capacity costs little on paper and saves rework later.

The pattern behind all ten: most mistakes are consistency failures between documents that were edited separately. That's why our workflow generates layouts, risers, and calculations from the same data — so they can't drift apart.